Sensing Principles and Industrial Transducers
2. Displacement, force, vibration and pressure
The LVDT (linear variable differential transformer) is the syllabus's signature displacement sensor: a moving ferromagnetic core changes the mutual inductance between a primary and two secondary windings, and the DIFFERENCE of the two secondary voltages, after phase-sensitive demodulation, gives a signal whose magnitude tracks displacement and whose polarity (recovered by comparing phase to the primary) tracks direction — a plain magnitude reading from an AC bridge could not tell which side of centre the core sits on. Force and torque are usually inferred from strain on an elastic member (a load cell, a torque shaft) via the bridge described above, and it is worth remembering that a well-designed strain-gauge bridge is arranged so temperature-induced strain cancels between arms while load-induced strain adds — temperature compensation built into the bridge topology itself, not bolted on afterward.
- A seismic (inertial) accelerometer, run well below its own natural frequency, reads acceleration directly; the same mass-spring-damper system, run well above its natural frequency, reads displacement instead — the two are the same hardware read in two different frequency regimes.
- Vibration and shock are the same physical phenomenon read differently — vibration as a sustained, often periodic quantity, shock as a single, brief, high-amplitude transient.
- Low-pressure and high-pressure measurement use different transducer families entirely, because a diaphragm or Bourdon tube sized for a high range would show negligible deflection at a low one.
3. Flow measurement, by four different principles
| Type | Depends on | Note |
|---|---|---|
| Variable head (orifice, venturi) | pressure drop across a restriction | flow is proportional to the SQUARE ROOT of the pressure drop |
| Variable area (rotameter) | a float's equilibrium position in a tapered tube | reads directly, roughly linear with flow |
| Electromagnetic | Faraday's law: emf induced by a conductive fluid moving through a magnetic field | needs a CONDUCTIVE fluid; no obstruction in the pipe |
| Ultrasonic (transit-time) | difference in sound transit time with and against the flow | non-intrusive, works from outside the pipe |
| Turbine | a rotor's speed of rotation, proportional to flow velocity | moving parts, needs periodic maintenance |
The electromagnetic flowmeter's one hard requirement — a conductive fluid — is also its one clean advantage: with no moving parts and no obstruction placed in the flow path, it introduces no pressure drop of its own and nothing to wear out, which is exactly why it is preferred for slurries and corrosive liquids that would foul or erode a mechanical meter.
4. Temperature and process-analytical measurement
| Sensor | Principle | Character |
|---|---|---|
| Thermocouple | Seebeck effect: emf from a junction of two dissimilar metals | wide range, needs cold-junction compensation |
| RTD | metal resistance rises nearly linearly with temperature | very accurate, needs lead-resistance compensation |
| Thermistor | semiconductor resistance falls sharply (usually) with temperature | highly sensitive, narrow range, non-linear |
| Pyrometer | radiated thermal energy from the target | non-contact; the only choice above a thermocouple's own melting point or for a moving target |
| Bolometer | resistance change of an element heated by absorbed radiation | detects radiant power itself, used in radiation thermometry and IR detection |
| Semiconductor (IC) sensor | a diode/transistor junction's predictable voltage-temperature relation | cheap, linear, narrow range, common in consumer electronics |
Beyond temperature, process instrumentation measures liquid level (by float, by differential pressure at the tank base, by capacitance between a probe and the tank wall, or by ultrasonic/radar time-of-flight from above), pH (by the voltage of a glass electrode against a reference electrode, following the Nernst equation), conductivity (by the current between two electrodes at a known applied voltage, which tracks dissolved ion concentration) and viscosity (typically by the drag a rotating or vibrating element experiences in the fluid, or by the time a fixed volume takes to flow through a capillary).
Key takeaways
- A handful of physical principles — resistive, capacitive, inductive, piezoelectric, electromagnetic, Hall-effect — cover almost the entire catalogue of named transducers.
- A piezoelectric sensor's charge leaks away over time, so it reads dynamic force, vibration and shock well but cannot hold a true static reading.
- An LVDT's phase-sensitive demodulation recovers direction, not just magnitude — a plain magnitude reading cannot say which side of centre the core sits on.
- Variable-head flowmeters follow a square-root law, so halving flow quarters the pressure signal — a narrower usable turndown than a rotameter or turbine meter.
- An RTD needs 3- or 4-wire connection because its own lead resistance is otherwise large enough to corrupt the reading; the 4-wire form removes it entirely.
- A thermocouple's emf tracks the temperature DIFFERENCE between two junctions, never one junction's absolute temperature — cold-junction compensation is mandatory, not optional.
Practice questions (9)
Attempt each one before opening the answer. Every explanation names the tempting wrong option as well as the right one, because that is where marks are lost.
A piezoelectric force sensor is a poor choice for measuring a truly static (constant, unchanging) load because
Show answer
Answer: B — its charge output leaks away through finite resistances, so the reading decays over time
The charge a piezoelectric sensor generates under stress leaks away through its own and the measuring circuit's finite resistance, so a constant applied force produces a signal that decays rather than one that stays steady — which is exactly why it suits dynamic (changing) loads and not static ones. It does generate charge under stress, has no such temperature restriction, and needs no external magnetic field.In an LVDT, phase-sensitive demodulation (rather than simple magnitude detection) is used specifically to recover
Show answer
Answer: B — the direction of displacement from the null position
Magnitude alone is the same on either side of the null position, so it cannot say which way the core has moved; comparing phase against the primary excitation resolves that ambiguity and recovers the sign (direction) of displacement, which is exactly what phase-sensitive demodulation is for.A well-designed strain-gauge load-cell bridge is arranged so that
Show answer
Answer: B — temperature-induced strain cancels between arms while load-induced strain adds
The whole point of a properly arranged multi-arm bridge is that gauges are placed so a temperature change affects all active arms the same way and cancels out of the bridge output, while mechanical load strains the arms in opposing senses (tension versus compression) so their contributions add — temperature compensation is built into the arrangement itself. A one-arm-active (quarter) bridge is a valid but less sensitive and less temperature-compensated configuration, and a properly zeroed bridge balances at no load, not the reverse.Halving the flow rate through a variable-head (orifice or venturi) flowmeter changes the differential pressure signal to
Show answer
Answer: B — a quarter of its full-flow value
Flow through this family of meter is proportional to the SQUARE ROOT of the differential pressure, so pressure is proportional to the SQUARE of flow — halving the flow reduces the pressure signal to (1/2)^2 = 1/4 of its original value, not a half. This square-law relationship is exactly why these meters have a comparatively narrow usable turndown ratio.An electromagnetic flowmeter has one hard requirement on the fluid, which is that it must be
Show answer
Answer: B — electrically conductive
The meter works by Faraday's law, inducing an emf as a conductive fluid moves through an applied magnetic field, so a non-conductive fluid produces no usable signal at all. There is no requirement of optical transparency, no fixed temperature ceiling of this kind, and viscosity is not the limiting property for this particular meter type.Above the melting point of the metals used in a thermocouple, or for a moving target, the appropriate temperature sensor is
Show answer
Answer: C — a pyrometer, which senses radiated energy without contact
A pyrometer measures radiated thermal energy from a distance, with no physical contact needed, which is exactly what is required both above any contact sensor's survivable temperature and for a target that is physically moving. RTDs, thermistors and semiconductor sensors all require direct physical contact and have their own, generally lower, temperature ceilings.A 4-wire (Kelvin) RTD connection eliminates lead-resistance error by
Show answer
Answer: B — separating the current-carrying leads entirely from the voltage-sensing leads
In a 4-wire connection, one pair of leads carries the excitation current and a separate pair senses the voltage across the RTD element with negligible current (and hence negligible voltage drop) flowing in them — so lead resistance, however large, contributes essentially nothing to the measured voltage. Wire thickness helps but does not eliminate the error; a fixed reference temperature and removing excitation current are not how this method works.A thermocouple's Seebeck emf is fundamentally a function of
Show answer
Answer: B — the temperature DIFFERENCE between the hot and cold (reference) junctions
The Seebeck effect produces an emf proportional to the temperature difference between the two junctions, which is exactly why cold-junction compensation — accounting for the reference junction's own temperature — is mandatory to recover the hot junction's actual temperature. It is not a function of wire resistance or of any external supply voltage.A glass-electrode pH measurement fundamentally reads
Show answer
Answer: B — a voltage between the glass electrode and a reference electrode, following the Nernst equation
pH measurement with a glass electrode is fundamentally a voltage (potentiometric) measurement between that electrode and a reference electrode, with the relationship between hydrogen-ion activity and voltage set by the Nernst equation. Conductivity measurement, not pH, is the current-based technique; viscosity and temperature alone are separate measurands entirely, though temperature does enter as a compensation term.